6-2
ELECTRICAL DATA
Revision Y06-02 Service Manual - KN Series
MODEL KN 36T KN 45T
Power Supply
To Outdoor To Outdoor
3PH – 400V – 50 Hz 3PH – 400V – 50 Hz
Max Current, A 3 x 11.9 3 x 17.5
Circuit Breaker 3 x 16 3 x 20
Power Supply Wiring
No. X Cross Section mm
2
5 X 2.5 mm
2
5 X 2.5 mm
2
Interconnecting Cable RC
Model No. X Cross Section
mm
2
6 X 1.5 mm
2
+ 2 X 0.5 mm
2
(OCT Sensor) 6 X 1.5 mm
2
+ 2 X 0.5 mm
2
(OCT Sensor)
Interconnecting Cable ST
Model No. X Cross Section
mm
2
5 X 2.5 mm
2
+ 2 X 0.5 mm
2
(OCT Sensor) 5 X 1.5 mm
2
+ 2 X 0.5 mm
2
(OCT Sensor)
6.4 Three Phase Units + Optional Heating Element
MODEL KN 24T KN 30T
Power Supply
To Outdoor To Outdoor
3PH – 400V – 50 Hz 3PH – 400V – 50 Hz
Heating Element, kW 2.1 2.7
Max Current, A 3 X 10.1 3 X 14.6
Circuit Breaker 3 X 16 3 X 16
Power Supply Wiring
No. X Cross Section mm
2
5 X 1.5 mm
2
5 X 2.5 mm
2
Interconnecting Cable RC
Model No. X Cross Section mm
2
6 X 1.5 mm
2
+ 2 X 0.5 mm
2
(OCT Sensor) 6 X 1.5 mm
2
+ 2 X 0.5 mm
2
(OCT Sensor
Interconnecting Cable ST
Model No. X Cross Section mm
2
5 X 1.5 mm
2
+ 2 X 0.5 mm
2
(OCT Sensor) 5 X 1.5 mm
2
+ 2 X 0.5 mm
2
(OCT Sensor)
MODEL KN 36T KN 45T
Power Supply
To Outdoor To Outdoor
3PH – 400V – 50 Hz 3PH – 400V – 50 Hz
Heating Element, kW 3.0 3.0
Max Current, A 3 X 16.2 3 X 21.9
Circuit Breaker 3 X 20 3 X 25
Power Supply Wiring
No. X Cross Section mm
2
5 X 2.5 mm
2
5 X 2.5 mm
2
Interconnecting Cable RC
Model No. X Cross Section mm
2
8 X 1.5 mm
2
+ 2 X 0.5 mm
2
(OCT Sensor) 8 X 1.5 mm
2
+ 2 X 0.5 mm
2
(OCT Sensor
Interconnecting Cable ST
Model No. X Cross Section mm
2
7 X 1.5 mm
2
+ 2 X 0.5 mm
2
(OCT Sensor) 7 X 1.5 mm
2
+ 2 X 0.5 mm
2
(OCT Sensor)
(1) The power supply to the heating element kit is provided separately from the main power supply unit.
NOTE
Power wiring cord should comply with local lows and electrical regulations requirements.