CONTROL SYSTEM
11-5
SM SAFRPM 1-A.0 GB
11.8 “SLEEP” mode
When the SLEEP button is pressed, the SLEEP mode is selected as following:
1. The indoor fan speed is set at the low speed, the power lamp and the sleep lamp is on, the
temperature off after 5 minutes.
2. When selecting COOLING/DRY operation with SLEEP mode, the set temperature will be raised by
1
O
C 1 hour later and 2
O
C 2 hour later.
3. When selecting HEATING operation with SLEEP mode, the set temperature will be dropped by 1
O
C
1 hour later and 2
O
C 2 hour later.
4. After the system operates in SLEEP mode for 8 hours, it will stop automatically.
11.9 Fan motor control
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the
microprocessor to feedback the rotational frequency. Comparing the current rotational frequency with
the target rotational frequency, the microprocessor adjusts fan motor electric to make the current
rotational frequency close to the target rotational frequency. With this control, when the fan speed is
switched, the rotational frequency changes smoothly.
(2) When the rotational frequency feedback signal has not output for 5 seconds (or when the
microprocessor can’t detect the signal for 5 seconds), the fan motor is regarded locked-up. Then the
electric current to the fan motor is shut off. 10 second later, the electric current is applied to the fan
motor again. During the fan motor lock-up, the POWER indicator lamp flashes on and off 6 times/cycle
or E6 to show the fan motor abnormality.
11.10 Auto fan speed control
11.10.1 When the auto fan speed is selected,
the indoor fan motor speed is automatically controlled by the room temperature and the set
temperature.
11.10.2 In COOLING mode,
the indoor fan motor operates as following:
11.10.3 In HEATING mode, the indoor fan motor operates as following:
11.11 Auto vane operation control
11.11.1 Vane motor drive
The unit is equipped with a stepping motor for the vane. The rotating direction, speed, and angle of the
motor are controlled by pulse signal transmitted from indoor microprocessor.