PERFORMANCE DATA & PRESSURE CURVES
5-5
SM SAFRPM 1-A.0 GB
5.3 SAF045 / GC 45 R22
5.3.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
Entering Air DB
OD Coil (
o
C)
Data
Entering Air WB/DB ID Coil (
o
C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
13.49 13.97 14.30 14.64 14.86
SC 9.55 9.96 10.34 10.60 10.80
PI 3.23 3.24 3.25 3.25 3.27
20
(1)
TC 13.05 13.76 14.19 14.53 14.84
SC 9.36 9.87 10.28 10.57 10.77
PI 3.51 3.52 3.53 3.55 3.56
25
TC 12.35 13.33 14.02 14.44 14.80
SC 9.12 9.67 10.20 10.50 10.69
PI 3.79 3.82 3.85 3.87 3.90
30
TC 11.55 12.58 13.59 14.07 14.49
SC 8.83 9.39 9.98 10.27 10.47
PI 4.09 4.15
4.19
4.22 4.26
35
TC 10.69 11.60
12.80
13.44 14.08
SC 8.40 9.00 9.75 10.03 10.23
PI 4.41 4.49
4.56
4.59 4.62
40
TC 9.72 10.59
11.55
12.63 13.28
SC 7.92 8.52 9.22 9.52 9.71
PI 4.76 4.83 4.92 4.98 5.03
46
TC 8.44 9.22 10.14 11.21 12.08
SC 7.29 7.81 8.41 8.70 8.90
PI
5.20 5.28 5.40 5.48 5.54
LEGEND
TC – Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OD – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, Optional Accessories are needed.