CONTROL SYSTEM
11-1
SM SAFRPM 1-A.0 GB
11. CONTROL SYSTEM
11.1 SAFETY CONTROL
11.1.1 Time delay safety control
a. 3 minutes delay for compressor—the compressor is ceased for 3 minutes to balance the
pressure in the refrigenration cycle in order to protect the compressor.
b. 2 minutes delay for 4-way valve—The 4-way valve is ceased for 2 minutes to prevent the
refrigenrant-gas abnormal noise when the HEATING operation is OFF or switch to the other operation
mode.
11.1.2 Indoor pipe temperature sensor frost prevention control
When the indoor pipe temperature sensor reads 0
O
Cor below for 5 minutes, the indoor pipe temperature
sensor frost prevention control starts. The compressor and outdoor fan stop and the indoor fan operates
at high speed for 3 minutes. After that, if the indoor pipe temperature sensor reads less than 5
O
C this
control prolonged until the indoor pipe temperature sensor reads 5
O
C or more.
11.1.3 High temperature protection control
During HEATING operation, the outdoor fan motor and compressor are controlled by the indoor pipe
temperature to prevent the high temperature of compressor.
Outdoor fan OFF: when the indoor pipe temperature is 53
O
C Outdoor fan ON: when the indoor pipe
temperature is 48
O
C Compressor OFF: when the indoor pipe temperature is 62
O
C Compressor ON:
when the indoor pipe temperature is 48
O
C
11.2 “I Feel” Model Operation
11.2.1 When the “I Feel” mode is selected,
the operation mode and initial set temperature
are determined by the initial room temperature at start-
up of the operation except to turn off the air conditioner and operates it again.
11.2.2 If the mode is change to “I Feel” mode form other mode,
the “I Feel” mode doesn’t operate until compressor stop for more than 3 minutes
In the “I Feel” mode, when the controller receives the up or down single of temperature, the set
temperature can adjust by 1
O
C upper or lower. The biggest you can adjust by 2
O
C upper or lower.
11.3 “COOLING” Mode Operation
11.3.1 When the COOLING mode is selected without setting temperature,
the system will set the set temperature at 26
O
C automatically with the AUTO FAN speed.
11.3.2 When selecting the COOLING mode operation,
the system will operate according to the setting by the remote controller and the operation is as
following: