5-10
PERFORMANCE DATA & PRESSURE CURVES
SM DNGRPM 1-E.4 GB
5.7.2 Heating
ENTERING
WB OD
COIL(
O
C)
ENTERING AIR DB ID COIL(
O
C)
15 20 25
TH Pl TH Pl TH Pl
-10 5.20 2.24 5.00 2.39 4.80 2.51
-7 5.59 2.30 5.40 2.42 5.20 2.55
-2 5.94 2.32 5.74 2.46 5.54 2.60
2 7.23 2.44
6.93 2.59
6.63 2.74
6 9.27 2.62 9.00 2.80 8.69 2.97
10 10.08 2.76
9.81 2.95
9.54 3.16
15 10.89 2.88 10.62 3.11 10.35 3.30
20 11.48 2.97 11.21 3.22 10.89 3.47
LEGEND
TH Total Heating Capacity, kW
PI Power Input, kW
WB Wet Bulb Temp., (
o
C)
DB Dry Bulb Temp., (
o
C)
ID Indoor
OD Outdoor
5.8 Capacity Correction Factor Due to Tubing Length
5.8.1 Cooling
TOTAL TUBING LENGTH (One Way)
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.01
1
0.98 0.97 0.96 0.95 0.94 0.93 0.9
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.8.2 Heating
TOTAL TUBING LENGTH (One Way)
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.02
1
0.99 0.99 0.98 0.97 0.97 0.96 0.95
* Minimum recommended tubing length between indoor and outdoor units is 3m.